Elkhart
Pressure-Matic® Valves
Pressure-Matic is a true pressure reducing 1½" or 2½"
valve. operated automatically by inner hydraulic controls. No
diaphragms, springs or outside controls are involved with the
unit, the action being completely dependent upon conditions at
the nozzle or sprinkler system. Outlet pressure up to 230 P.S.I.
is controlled under all flow and no-flow situations.
The Pressure-Matic valve, constructed entirely of brass, is
completely tamper-proof. It fits all existing cabinets where 1½"
or 2½" valves are used. Its open height is no greater than
existing fire department hose valves. UR-20 and UR-25 valves are
available to handle water inlet pressure up to 400 P.S.I. which
exceeds the highest allowable pressure under NFPA Standard #14.
The Pressure-Matic with United States and Canadian patents,
is applicable for installation in buildings of any height. It is
listed or approved by: Underwriters' Laboratories Inc., New York
City Board of Standards and Appeals, and Underwriters'
Laboratories, of Canada.
Pressure-Matic meets the requirements of NFPA Standard #14,
paragraph 2-1.3, extending zone heights from 275' to 400' thus
reducing the number of zones required. It fits standard size
fire cabinets. Pressure-Matic also functions as a shut-off valve
as well as a pressure-regulating valve under both flow and
no-flow conditions. It also simplifies testing. When Pressure-Matic
valves are used in a fire protection system, the system can be
hydrostatically tested at 200 P.S.I. or more as called for by
NFPA Standard #14, paragraph 7-1.1. It is not necessary to
disassemble or blank off the valve or to take other steps to
protect internal parts. Automatic Signal Function Bracket and
Visual indicator are available as options.
(A) Supervised Capability Function
When equipped with bracket and switch, the Pressure-Matic
valve can be used in a supervised system to produce an audible
and/or visual alarm in case the valve is closed.
(B) Automatic Pressure Reducing Function
An outlet flowing or static pressure range of 20 to 230 P.S.I.
can be obtained depending upon inlet pressure and valve
selection.
(C) Automatic U.L. Listed Check Valve Function
U.L. listed as having automatic checking feature. When dual
risers are used and sprinklers are fed from both, Pressure-Matic
operates as a check valve to prevent loss of sprinkler pressure
in the event of damage to one riser.
IMPORTANT: When testing the sprinkler system for
pressure, Pressure-Matic® can be subjected to back pressure up
to its full rating (400 P.S.I.) without damage to the valve.
(D) Floor Control Valve
Pressure-Matic provides a floor control valve in an automatic
sprinkler system and both 1½" and
2½" sizes are listed by Underwriters' Laboratories for
such use. It is equipped with a visible indicator to show valve
attitude. The 1½" valve can be used for flows up to 200
G.P.M. and the 2½" size up to 500 G.P.M. The sprinkler
system can be pressure tested as required in NFPA Standard #13,
paragraph 1-11.3 with back pressure up to full 400 P.S.I. rating
of Pressure-Matic without damaging the valve. Pressure-Matic
also operates as a check valve at pressures up to 400 P.S.I. in
dual standpipe systems where sprinklers are fed from both to
prevent loss of sprinkle pressure in case of damage to one
standpipe. Since it serves as a check valve, a floor control
valve and a pressure reducing valve, it can replace three valves
in many cases. In cases where the flows to sprinkler branch
lines are required to be over 200 G.P.M., the less expensive 1½"
Pressure-Matic fills the requirement and may be used.
An optional bracket allows the use of tamper switches.
Sprinkler pressures up to 230 P.S.I. may be obtained. When the
sprinkler system is in a static condition, a very minute leakage
past the seat of the pressure reducing valve can, because of the
incompressibility of water, result in a large pressure buildup
of the downstream side of the valve. In order to reliably
maintain the desired safe valve outlet pressure for long periods
of time under a static condition, a relief valve on the
discharge side of the pressure reducing valve is considered
necessary.
(E) Standpipe Systems
Class I-- For use by trained fire personnel. The
2½" Pressure-Matic provides Class I service as outlined by
NFPA Standard #14, Pressure-Matic meets the requirements of NFPA
Standard #14 paragraph 2-1.3, extending zone heights required.
The valve fits standard size fire cabinets.
Pressure-Matic acts as a shut-off valve as well as
pressure-regulating valve under both flow and no-flow
conditions. It provides for simplified testing, too. When
Pressure-Matic valves are used in a standpipe system the system
can be hydrostatically tested at 200 P.S.I. or more as called
for by NFPA Standard #14, paragraph 7-1.1. It is not necessary
to disassemble or blank off the valve or to take other steps to
protect internal parts.
Automatic Signal Function Bracket and Visual Indicator are
available as options.
Class II-- For use by building occupants. The 1½"
Pressure-Matic meets the requirements for Class II service as
outlined by NFPA Standard #14. The valves control the pressure
to 1½" hose rack units under both flow and no-flow
conditions thus allowing the use of rubber lined hose, shut-off
nozzles, and periodic testing.
Class III-- For use by building occupants and trained
fire personnel. The 2½" Pressure-Matic valve provides
Class III service as outlined by NFPA Standard #14. The valve
controls nozzle pressure for the use of 1½" hose and
nozzle by building occupants. The 2½" X 1½" hose
reducer can be removed, together with the 1½" hose, and
out any valve adjustment under flow and no-flow conditions of
the 2½" line used by the Fire Department.
Finish: Cast Brass
Optional Finish: Polished brass, rough chrome plated or polished
chrome plated.
Automatic Sprinkler Systems
Pressure-Matic provides a floor control valve in an automatic
sprinkler system and both 1½" and 2½" sizes are
listed by Underwriters' Laboratories for such use. It is
equipped with an open/close visual indicator. The 1½"
valve can be used for flows up to 200 G.P.M. and the 2½"
size up to 500 G.P.M. The sprinkler system can be pressure
tested as required in NFPA Standard #13, paragraph 1-11.2 with
back pressure up to full 400 P.S.I. of Pressure-Matic without
damaging the valve. Pressure-Matic also operates as a check
valve at pressure up to 400 P.S.I. in dual riser systems where
sprinklers are fed from both to prevent loss of sprinkler
pressure in case of damage to one riser. Since it serves as a
check valve, a floor control valve and a pressure reducing
valve, it can replace three valves in many cases. The new
straight pattern body allows greater versatility and economy in
locating the floor control valve installation. In many cases
where flows to sprinkler branch lines are not required to be
over 200 G.P.M., the less expensive 1½" Pressure-Matic
Angle Valve fills the requirement and may be used. An
optional bracket allows the use of supervisory switches. U.L.I.
listed up to 400 P.S.I. All valves are factory tested at 600
P.S.I.